Heat Pump Outdoor Unit: Placement and Noise

8 min read
Illustration: an air-to-water heat pump outdoor unit on a concrete plinth with rubber anti-vibration feet and a gravel bed below, beside a rendered wall, in winter light and frost

Monobloc or split: what is the difference for the house?

With an air-to-water heat pump, the first decision is the type. Regulation (EU) 2024/573 on fluorinated greenhouse gases uses two terms. A self-contained unit is a complete factory-made system in which the installer connects no gas-containing parts on site (Art. 3 point 38). A split system is several units connected by refrigerant piping. The installer installs and connects parts of the refrigerant circuit at the point of use (Art. 3 point 39).

For the house this means two different solutions. A monobloc keeps all its refrigerant outside and sends heating water into the house. A split sends refrigerant into the house and the water stays inside. With a monobloc, there is water outdoors that can freeze. The installation manual of one monobloc with R290 refrigerant states that the factory-fitted freeze protection valves protect the outdoor unit, not the field piping. More valves must go at all lowest points of the piping, and this manual forbids adding anti-freeze, for example glycol, to the water. With a split, the question is different: who may connect the refrigerant circuit.

AspectMonobloc (self-contained)Split
What runs between the unit and the houseHeating circuit waterRefrigerant piping
Refrigerant circuit connected on siteNo, the installer connects no gas-containing parts on site (Art. 3 point 38)Yes, the installer installs and connects the circuit at the point of use (Art. 3 point 39)
What to watch outdoorsFrozen water: freeze protection valves at the lowest points of the piping (manufacturer manual)Only a certified person may install a circuit with fluorinated gas (Art. 10)
Ban on placing on the market up to 12 kW with fluorinated gas of GWP 150 or moreFrom 1 January 2027 (Annex IV point 8(b))From 1 January 2027 for air-to-water split (Annex IV point 9(b))
Ban on placing on the market up to 12 kW with any fluorinated gasFrom 1 January 2032 (Annex IV point 8(c))From 1 January 2035 (Annex IV point 9(d))

The bans under Art. 11(1) apply to placing products on the market, not to running a unit that is already installed. Each of them has an exception where safety requirements at the site of operation demand it.

Sound power or sound pressure: which number do you compare?

The energy label of a heat pump shows the sound power level. Regulation (EU) No 813/2013 defines it as the A-weighted sound power level, indoors and/or outdoors, expressed in dB (Art. 2 point 22). It is a property of the source. The sound pressure level is what a sound level meter reads at a given point, and it depends on distance, reflections and obstacles. So the neighbour hears pressure at their window, not the power on the label.

The same regulation sets a maximum outdoor sound power from 26 September 2015. It is 65 dB for heat pumps up to 6 kW rated heat output, and 70 dB above 6 kW up to 12 kW. LAI is the German federal and state working group on immission control. Its 2023 guide says that units well below 50 dB(A) sound power are on the market. It also warns that the label value is not always the maximum. If the manufacturer also gives a maximum value and night operation at that level cannot be ruled out, the assessment should use that value.

A catalogue sound pressure value holds only for the conditions of its test. The manufacturer manual warns that a measurement at the real site can show more than the catalogue value, because of ambient noise and sound reflections. When you compare offers, compare sound power and ask for its maximum value. A quiet night mode lowers noise, but according to the LAI guide it can also noticeably lower seasonal efficiency.

How much noise may reach the neighbour's window?

In Slovakia, decree No 549/2007 Coll. of the Ministry of Health applies. The space in front of the windows of living rooms in family houses is area category II (Annex, Table 1). The same category covers outdoor space in residential and recreational areas. For noise from sources other than transport, the permitted equivalent level is 50 dB by day and in the evening, and 45 dB at night. Day runs from 6:00 to 18:00, evening from 18:00 to 22:00 and night from 22:00 to 6:00. The measuring point in front of an external wall lies 1.5 m ± 0.5 m from the wall. It lies 1.5 m ± 0.2 m above the floor of that storey (§ 6(3)(b)).

For tonal or especially disturbing noise, the assessment adds a correction of +5 dB to the equivalent level (Table 2). The decree gives the intermittent running of a compressor as an example of intermittent noise. It describes tonal noise as sound to which a listener can subjectively assign a pitch. So the night limit at the neighbour's window is what decides. The post on acoustics in a family house explains how the decree treats noise inside the house.

How do walls, corners and distance change what the neighbour hears?

The LAI guide is German and its limits are German, but sound travels the same way everywhere. Its emission level of a unit starts from the sound power. It subtracts the effect of a blocked line of sight and adds the effect of reflections and tonal components. A table then gives the minimum distance to the neighbour's window from that level: the higher the level, the further away the unit must stand.

Situation at the unitAdjustment to the emission level (LAI)
No reflecting surface closer than 3 m (for example in the garden)0 dB
One reflecting surface closer than 3 m (in front of a house wall)+3 dB
Two reflecting surfaces closer than 3 m or at most 5 m apart (corner, between two walls, under a canopy)+6 dB
Direct line of sight to the neighbour's window0 dB
Indirect line of sight−5 dB
No line of sight, for example blocked by a building−15 dB
Tones perceptible, or clearly audible (if nothing is known, use 3 dB)+3 dB, or +6 dB

A corner between two walls therefore adds 6 dB, the same as a unit with 6 dB more sound power. A screen works only if it stands as close to the source as possible and is larger than the source. If it blocks the line of sight and stands right next to the source, it lowers the rating level by about 10 dB. Next to a house wall, though, a screen can cause multiple reflections, so its side facing the unit gets an absorbing lining. Neither a screen nor an enclosure may restrict airflow to the heat exchanger, or the unit loses capacity and its noise can rise.

Where should the outdoor unit stand, and on what?

The LAI guide says the unit, its air inlet and its outlet should stand far from the neighbour's protected spots. Ideally they face away from them. The guide adds that a position towards the street often makes sense, because bedrooms and terraces usually face away from the street. The manufacturer manual forbids placing the unit near noise-sensitive areas, for example a bedroom, and in a basement. In a place exposed to wind, the air inlet and outlet should be perpendicular to the main wind direction, with wind protection if needed.

The base under the unit matters. The LAI guide advises against hard surfaces such as concrete, tiles or asphalt and prefers a gravel bed, grass or bark mulch. The guide says to decouple unit and ground acoustically. One way is an elastic bearing of the concrete slab on rubber feet, with no rigid bridges such as bolted joints. The unit should not stand on a floating screed with impact sound insulation, and a joint around its base should separate it. Pipes should hang on elastic supports, not in rigid clamps. One monobloc manual requires at least 150 mm of free space under the unit and at least 100 mm above the highest expected snow level.

Choose the spot while laying out the plan. Put the plant room close to the unit, keep the piping short, keep the unit away from bedroom windows and leave room for service. The distance from the plot boundary follows from sound power, reflections and the position of the neighbour's windows, not from one set number.

What happens to ice and condensate during defrosting?

The heat exchanger of the outdoor unit ices up in winter, so the unit regularly runs a defrost cycle. The LAI guide says that icing and automatic defrosting usually cause disturbing sounds different from normal running. In some units this happens regularly at outdoor temperatures below 10 °C.

Defrosting releases water. The manufacturer manual requires that condensate can drain away properly. In a cold climate it recommends insulating the drain hose and adding a drain heater so that the condensate cannot freeze. The drain hole in the bottom plate must not be covered. Plan at the design stage where the drain leads, so that the condensate does not freeze on a path or step.

What protective zone does a unit with R290 refrigerant need?

R290 is propane. Regulation 2024/573 gives it a GWP of 0.02 in Annex VI. The manufacturer manual places it in safety class A3 as defined in ISO 817 and used in EN 378. So a protective zone applies around the outdoor unit in case of an unlikely leak. According to this manual, the zone must not contain:

  • openings into habitable areas: openable windows, doors, ventilation openings, basement entrances.
  • ignition sources, even brief ones: open flames, electrical installations, sockets, lamps, switches, the electrical house connection, sparking tools and surfaces hotter than 360 °C.
  • adjacent buildings and public traffic areas, which the zone must not reach.
  • units of another type, with another refrigerant or from another manufacturer.

The shape and size of the zone depend on the installation, for example in front of a wall, in a corner or on a roof. The manufacturer gives them for each model. So an R290 unit cannot be moved closer to a window without checking the zone. With a house close to the boundary, the zone can decide the position before noise does.

What should you ask the installer before signing?

  1. What is the outdoor sound power level on the label, and what is the maximum value, especially at night?
  2. Does the unit have tonal components or marked low-frequency noise?
  3. Which refrigerant does the unit use, and what protective zone does the manual give?
  4. For a split: who connects the refrigerant circuit, and do they hold a certificate under Art. 10 of Regulation 2024/573?
  5. For a monobloc: where will the freeze protection valves go, and how is the outdoor piping insulated?
  6. Where will the condensate go, and does the drain have a heater?
  7. What base will the unit stand on, and with what elastic bearing?

Check noise and the protective zone at the design stage. The unit is part of the whole energy concept in the passive house guide. If the neighbour's bedroom lies close to the boundary, a specialist can calculate the level at their window as part of a noise study.

Frequently asked questions

Does a heat pump outdoor unit need a permit?
Building Act 25/2025 exempts some devices (§ 18(5)(i)). They need no decision on the building intent and no notification. The devices are those that produce electricity, heat and cooling from renewable sources, up to and including 50 kW of total installed output. Directive (EU) 2018/2001 counts the aerothermal energy that heat pumps capture as energy from renewable sources (Annex VII). This is the version in force from 1 November 2025 to 31 December 2026. A new version applies from 1 January 2027, so check it before installation. The exemption does not change the noise limits of decree 549/2007.
What is the bivalence point and when is a backup heater needed?
Regulation (EU) No 813/2013 defines the bivalent temperature as the outdoor temperature that the manufacturer declares. At that temperature the declared capacity equals the part load. Below it, the unit needs supplementary capacity. Below the bivalence point, a supplementary heater helps. The regulation also defines the operation limit temperature, below which an air-to-water heat pump delivers no heating capacity. Ask for both values from the data sheet.
Does a hedge work as a noise screen?
No, according to the LAI guide. Hedges, trees or other planting between the unit and the window do not lower the noise in a relevant way. The same guide says that planting on a facade has practically no sound-absorbing effect either.
Is it worth putting the unit in an enclosure?
The LAI guide says that an optimally designed enclosure lowers the rating level by about 20 dB. It needs a sound-absorbing inner surface and sealed penetrations, and the unit inside should sit on an elastic bearing. It must not restrict airflow, so the guide recommends consulting an expert in refrigeration plant acoustics.
Why can I hear the unit through a closed window?
The LAI guide says that low-frequency noise comes mainly from the compressor, and windows and walls shield it poorly. It is worth asking the manufacturer about it. Some manufacturers offer models in which the compressor is part of the indoor unit.
Does the fluorinated gas ban apply to the unit I already have?
The bans under Art. 11(1) of Regulation (EU) 2024/573 apply to placing products on the market. The same paragraph allows placing on the market parts needed for repair and servicing of existing equipment, under the conditions it sets.
Who may connect a split heat pump?
Under Art. 10(1) of Regulation (EU) 2024/573, a natural person who installs, services or repairs a stationary heat pump with fluorinated gas must be certified. Under Art. 10(2), the company that carries out this work also needs a certificate.
Can the unit run in quiet mode at night?
Yes. If the manufacturer guarantees it, the LAI guide allows the lower night sound power to be used. It warns, however, that quiet mode can noticeably lower efficiency. The guide also says that an additional buffer tank can reduce switching and running at night.

Sources

  1. Regulation (EU) 2024/573 on fluorinated greenhouse gases · European Parliament and Council (Official Journal of the EU) · Art. 3 points 38 and 39, Art. 5(2), Art. 10(1) and (2), Art. 11(1), Annex IV points 8 and 9, Annex VI
  2. Commission Regulation (EU) No 813/2013, ecodesign requirements for space heaters and combination heaters · European Commission (Official Journal of the EU) · Art. 2 point 22, Annex I definitions, Annex II point 3
  3. Vyhláška MZ SR č. 549/2007 Z. z., ktorou sa ustanovujú podrobnosti o prípustných hodnotách hluku, infrazvuku a vibrácií · Ministerstvo zdravotníctva SR (Slov-Lex) · § 2 písm. v), x), zh), § 3 ods. 1, § 4 ods. 1, § 6 ods. 3 písm. b), príloha tabuľka č. 1 a č. 2
  4. Leitfaden für die Verbesserung des Schutzes gegen Lärm bei stationären Geräten (Langfassung), Stand 28.08.2023 · Bund/Länder-Arbeitsgemeinschaft für Immissionsschutz (LAI) · Chapters 2, 3.3.3, 4.1 to 4.2, 6.1 to 6.3.4
  5. Installation manual, Daikin Altherma 4 H (EPSKS04-07A V3), 4P820802-1, 2025.08 · Daikin Europe N.V. · Chapters 3.1, 4.1.1, 4.2.1, 4.2.3, 5.1
  6. Zákon č. 25/2025 Z. z. Stavebný zákon · Národná rada SR (Slov-Lex) · § 18 ods. 5 písm. i)
  7. Directive (EU) 2018/2001 of the European Parliament and of the Council of 11 December 2018 on the promotion of the use of energy from renewable sources · Official Journal of the European Union · Annex VII

Topic

  • Passive house and energy