Passive House Classes (Classic, Plus, Premium)

Passive House Classes are three grades of the Passive House Institute standard, set by renewable primary energy demand and on-site renewable generation.

What are the Passive House classes Classic, Plus and Premium?

Passive House Classes are three grades of the Passive House Institute (PHI) standard. They rank a building by its renewable primary energy demand and its renewable energy generation. A building is Classic, Plus or Premium.

PHI is a private institute in Darmstadt, Germany. Its certification is voluntary and separate from Slovak law. All figures on this page come from the PHI document "Criteria for Buildings", Version 10c, January 2023, valid with PHPP 10. The PHI download page lists it as the current version on 31 October 2026.

The same document also defines the Passive House energy demand limits. A building must meet them in every class. Only the renewable energy part differs.

What is the difference between Classic, Plus and Premium?

The classes differ in two limits. Plus and Premium need a lower renewable primary energy (PER) demand than Classic, and they need on-site renewable generation. Classic needs none.

CriterionClassicPlusPremium
PER demand, kWh/(m²a), at most604530
Renewable energy generation, kWh/(m²a) of building footprint, at leastnone required60120

PHI states these values in Table 1 of Section 2.1. The PER demand is per square metre of treated floor area. The generation is per square metre of projected building footprint.

What do the unit kWh/(m²a) and the abbreviation PER mean?

The unit kWh/(m²a) means kilowatt hours per square metre per year. PER means renewable primary energy. It states how much renewable energy a plant must first generate to cover all energy use of the building.

PER also counts losses from temporary storage, for example for seasonal storage. A low heating demand lowers the PER demand, because winter heat is hardest to supply from summer solar power. Passive solar design helps here.

The treated floor area (TFA) roughly matches the living or useful area. PHI uses the footprint for generation, because it matches the area available for solar panels. A single-storey house would otherwise gain an unfair advantage.

Which requirements are the same in all three classes?

Every class must meet the Passive House limits for heating, cooling, airtightness and summer comfort. Section 2.1 of the criteria gives these values.

  • Heating demand: at most 15 kWh/(m²a). The alternative is a heating load of at most 10 W/m², used together with the alternative cooling criterion.
  • Cooling and dehumidification demand: at most 15 kWh/(m²a) plus a variable allowance. The PHPP calculates the allowance from climate data and internal loads.
  • Airtightness: n50 of at most 0.6 per hour at a test pressure of 50 pascals. See airtightness.
  • Summer comfort: in a building without active cooling, at most 10 % of the hours in a year above 25 °C (Section 2.4.1).

A higher class does not relax these limits. It adds the renewable energy part on top.

How do you prove the renewable generation?

You calculate the expected yearly generation in the PHPP and submit evidence for it. For a photovoltaic system the evidence is the data sheets of the modules and inverters.

PHI treats a building off the grid and a building on the grid in the same way. It does not matter how much of the electricity the building uses itself. Grid feed-in counts like own use.

The generated energy is not subtracted from the demand. The PHPP calculation does allow some exchange between the two limits, explained below.

Can generation make up for a higher PER demand?

Yes, within limits. If the PER demand is above the class limit, the limit rises by at most 15 kWh/(m²a). The building must then generate the same difference on top of the standard generation requirement.

The reverse also works. A building with a lower PER demand may generate less, again by an amount equal to at most 15 kWh/(m²a). The two area references differ, so the PHPP compares them in absolute kWh per year.

Can the renewable energy come from outside the building?

Yes. Off-site generation counts if the system is new and the owner or long-term user owns it. A system that started operation before construction began does not count.

Biomass use, waste-to-energy plants and geothermal energy do not count as off-site generation. The counted amount follows the ownership share in the total investment.

Can a Classic building become Plus or Premium later?

Yes, in the certification process. A generation system must be ready for use when the certificate is issued. If it is not, the certifier may issue a Classic certificate first. It can later become a higher class after the system is complete (Section 3.2.9.c).

How do the classes work for EnerPHit retrofits?

EnerPHit, the PHI standard for retrofits, uses the same three classes. EnerPHit certifies renovated existing buildings. It does not certify entirely new buildings.

The PER and generation limits are the same as in the table above. The PER demand gets an extra allowance for the larger heating and cooling demand. The airtightness limit is n50 of at most 1.0 per hour (Table 4).

Under the energy demand method, the heating demand limit depends on the climate zone (Table 3). A retrofit may instead follow the component method of Table 2.

Climate zone in the PHPPHeating demand, kWh/(m²a), at most
Arctic35
Cold30
Cool-temperate25
Warm-temperate20
Warm, hot, very hot15

Which unit applies to the old 120 kWh/(m²a) value?

The 120 kWh/(m²a) value is a limit on non-renewable primary energy (PE), not on PER. PHI still allows PE as the proof for Classic, but not for Plus or Premium.

The PHPP holds country-specific PE limits. If it has none for a country, it uses 120 kWh/(m²a) with a primary energy factor of 2.6 for the electricity mix.

How do the classes relate to other energy terms?

The classes are not an EU or Slovak category. A nearly zero-energy building follows national law. The PHI classes follow PHI criteria. For the Slovak energy classes, see energy class.

The terms zero-energy house and plus-energy house have their own definitions. They do not equal Plus or Premium by definition. The PHI classes use the figures above.

Frequently asked questions

What is the difference between Passive House Classic, Plus and Premium?
Classic has a PER demand of at most 60 kWh/(m²a) and needs no renewable generation. Plus needs at most 45 and at least 60 kWh/(m²a) of generation. Premium needs at most 30 and at least 120 (PHI criteria, Version 10c, Table 1).
What does kWh/m²a mean in the Passive House criteria?
It means kilowatt hours per square metre per year. Demand values refer to the treated floor area. Renewable generation refers to the projected building footprint, so the two values cannot be compared directly.
Do all three classes have the same heating demand and airtightness limit?
Yes. Each class needs a heating demand of at most 15 kWh/(m²a) and an n50 airtightness value of at most 0.6 per hour. Only the PER demand and the generation differ.
Can I buy renewable energy elsewhere to reach Plus or Premium?
Partly. Only new off-site systems owned by the building owner or long-term user count. Existing systems do not count, and biomass, waste-to-energy and geothermal energy are excluded.
Can a Classic house be upgraded to Plus or Premium later?
Yes. If the generation system is not ready at certification, the certifier may issue a Classic certificate first. It can be converted to a higher class after the system is complete.
Do the classes also exist for renovations?
Yes. EnerPHit retrofits are also certified as Classic, Plus or Premium. They use the same PER and generation limits plus an allowance, and an airtightness limit of n50 at most 1.0 per hour.

Sources

  1. Criteria for Buildings: Passive House, EnerPHit, PHI Low Energy Building, Version 10c, January 2023, valid with PHPP 10 · Passive House Institute · Section 2.1 Table 1, Section 2.4.1
  2. Criteria for Buildings: Passive House, EnerPHit, PHI Low Energy Building, Version 10c, January 2023, valid with PHPP 10 · Passive House Institute · Section 2.2, Tables 3 and 4
  3. Criteria for Buildings: Passive House, EnerPHit, PHI Low Energy Building, Version 10c, January 2023, valid with PHPP 10 · Passive House Institute · Section 3.2.9 and extended version, PER method and area reference
  4. Building Certification: Building Criteria Version 10c · Passive House Institute