A blower door test measures how much air leaks through the building envelope at a pressure difference of 50 Pa. The n50 value comes from it. The test matters most when the airtight layer is finished and still accessible, because leaks can still be repaired at that stage.
What does a blower door test measure and what does n50 mean?
A blower door test is a pressure test of the whole building envelope. A fan creates a pressure difference in the building and the instrument measures the airflow at 50 Pa. The n50 value is this airflow divided by the air volume of the building. It is given in 1/h, that is, air changes per hour.
The result describes the airtightness of the building envelope. It does not show where air leaks. It only says how much leaks in total.
The standard ISO 9972 sets the measuring method. Passive House certification requires its method 1 with a few deviations, listed below. The text of the standard is paid, so we do not quote it here.
What n50 limit applies to a passive house and EnerPHit?
The Passive House Institute (PHI) sets the limits in its criteria, version 10c. They are voluntary standards. No law prescribes them.
| PHI standard | Highest n50 value |
|---|---|
| Passive House (Classic, Plus, Premium) | 0.6 1/h |
| EnerPHit (retrofit) | 1.0 1/h |
| PHI Low Energy Building | 1.0 1/h |
The criteria judge the average of the measurements at positive and negative pressure. The test covers the whole heated or cooled volume of the envelope. Measuring single parts of the house or taking over the result of a similar house is not enough.
When should you run a blower door test?
Straight after the airtight layer is complete, that is, after the windows are installed and the membrane in the roof is laid. PHI gives the reason: once floors, plaster and linings are finished, many junctions and penetrations cannot be repaired without demolition.
According to PHI, one measurement is normally enough. If there is concern that later work damaged the airtight layer, the measurement is repeated. Missing envelope parts at the time of the test worsen the result, and certification accepts such a result only in exceptional cases.
An older test can also be used for later certification. The condition is that no building work that could change the airtightness considerably has been done since.
How do you prepare a building for the test?
Seal only what must be closed for the measurement. That is usually the outdoor openings of the ventilation system: the fresh air intake and the exhaust air outlet. Every temporary seal must be recorded exactly. No other sealing of the envelope is allowed before the measurement, for example key holes or leaky windows.
The exception is temporary taping over a missing building part, for example a door threshold or a water trap. This too is documented in detail. If the ducts cannot be sealed, their leaks count towards n50.
What equipment is used, and how does the measurement run?
The Slovak testing institute TSÚS describes the test as relatively simple and safe for the building. It needs no physical destructive work on the structure. The equipment is an adjustable sealing frame, an airtight sheet with an opening, and a fan with automatic speed control.
- The ventilation openings and other envelope parts are prepared by the rules given above.
- The sealing frame with the airtight sheet and the fan goes into an open outside door, either an entrance door or a balcony door.
- The fan holds the set pressure difference between outside and inside, usually 50 Pa. It adds airflow according to how much air escapes through leaks in the envelope.
- A series of values is measured at negative and at positive pressure. The n50 value is the measured airflow divided by the building volume. For PHI certification the average of both measurements counts.
PHI sets no maximum difference between the positive and the negative pressure measurement.
What volume is n50 calculated from?
From the air volume inside the airtight layer, determined room by room. The floor area of a room is multiplied by its clear height. PHI does not allow a flat reduction factor on the gross volume. The dimensions are those of the finished building, even if the screed is not yet laid.
Spaces outside the airtight layer do not count, for example an unheated cellar, a porch or a conservatory outside the envelope. The air above suspended ceilings does not count either. That is why n50 values cannot be compared unless you know the volume they come from.
How are terraced houses, inaccessible rooms and large buildings tested?
A whole row of terraced houses may be certified as one building with one PHPP calculation. Then the test can cover all the houses together. The houses need openings between them that are large enough, for example installation penetrations, so that the pressure reaches the house farthest from the fan. If each house is certified on its own, each needs its own test.
Sometimes a smaller part of a building cannot be measured. The reason may be a store room with access only from outside, or a flat that nobody can enter on the agreed day. Under ISO 9972 as PHI applies it, the measurement is still valid in that case. The missing volume must be less than 5 % of the total volume Vn50. The report states the reason for the exclusion, the size of the missing area in m² or m³, and a description of the procedure.
For large buildings only the n50 limit applies. For buildings of 4,000 m³ or more, PHI recommends striving for a q50 of at most 0.6 m³/(h·m²). The q50 value refers to the envelope area. Tall buildings have special conditions, so contact the certifier.
Who can carry out the test?
For PHI certification, nobody who helped make the airtight envelope may run the test. This includes designers and tradespeople, because they would test their own work. The building owner and close family may not run it either. An energy consultant or the certifier may run it if they fall into neither group.
The instrument must be calibrated regularly as the manufacturer specifies. If too much time has passed since the last calibration, the result is not used for certification. The test report must also document the calculation of the air volume.
Which standard sets the measurement, and is a national version enough?
TSÚS states that the test follows STN EN ISO 9972:2016. The Slovak title is Tepelnotechnické vlastnosti budov. Stanovenie vzduchovej priepustnosti budov. Metóda pretlaku pomocou ventilátora. For PHI certification, method 1 of ISO 9972 always applies, with the deviations from the criteria.
In the national versions of the standard, method 3 contains national amendments. In Germany a test by method 3 also meets the certification requirements. PHI has not checked this for other countries, so method 1 applies there. Differing national rules, for example for determining the building volume, are not accepted for certification.
What do you do if the house does not reach the limit?
Find the leaks and repair them while they are accessible. For EnerPHit and PHI Low Energy Building with n50 between 0.6 and 1.0 1/h, and for pre-certification, PHI requires extensive leak detection during the test. Individual leaks that could cause structural damage or reduce comfort must be found and removed. The person who did the search signs a written note of this.
If the gap is large and sealing repairs do not help, the cause is often the design: the airtight layer is not continuous. That is a matter for the designer. In a deep renovation this is more common, because the original construction did not plan for an airtight layer. A vapour retarder is part of that layer.
How are leaks found during the test?
While the building is at negative pressure, leaks are easy to find. TSÚS names a wet hand or a smoke stick. An anemometer finds leaks more precisely. A thermal camera is useful for documenting the existing state.
The PHI sample statement for leak detection says that the tester inspected all rooms in the envelope. The tester also checked all points known to be prone to leaks. This includes hard-to-reach points such as tall ceilings. Any large leaks with a significant share of the total leakage, or affecting thermal comfort, were sealed.
Does the test make sense outside Passive House certification?
The standard STN 73 0540-2+Z1+Z2: 2019, Thermal protection of buildings, Part 2: Functional requirements, distinguishes eight quantities that secure the required thermal properties of buildings. One of them is the air permeability of joints in building structures. The text of the standard is paid, so we give no value from it.
According to TSÚS, leaks in the building envelope decide how much heat the building loses. They also cause moisture problems such as damp patches on surfaces or mould. They also worsen the airborne sound insulation of the structures. For this reason TSÚS recommends a check at the handover of a building. An objective test method, that is, a blower door test, locates the leaks.
Does Slovak law require a blower door test?
Act 25/2025 Z. z. in the version in force to 31 December 2026 contains neither the term airtightness nor n50, and it does not require a test. We did not find it in the text of decree 364/2012 Z. z. on energy performance of buildings either. The decree lists a measured n50 as an input in the report attached to the energy performance certificate. It sets no value a house must reach.
So you need a test when somebody verifies a claim about tightness: in PHI certification, or if a support programme asks for it. Read the conditions of the specific call before you order the test. The report form for the energy performance certificate in decree 364/2012 has a row for a measured n50 (Annex 4, rows 54 to 56). It lists the calculated and the assumed average air change rate n in separate rows.
The wider context is in the article Passive House from A to Z. For the ventilation decision, see also heat recovery ventilation.
